• Enter the Flame Strength, NOx and CO readings from the Combustion Analyzer and
multi-meter in the Manual Combustion Calibration screen’s Reading column.
• Enter the same values, plus the O
2
value, on the Combustion Calibration Data Sheet
provided with the unit.
24. Lower the Valve Position to the next calibration point using the (Left) arrow key (if using
Method 1 in step 11) or the Fine Valve Position – (Minus) key (if using Method 2).
• BMK750 & 1000: 80%
• BMK1500 – 6000: 70%
25. Repeat step 17, 18 and 21 at that valve position and the rest of the valve positions in Table
4-3a through 4-3d, depending on model. The O
2
, NOx and CO should stay within the
ranges shown in these tables.