Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OMM-0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 92 of 153
OPTION 2 Instructions: Constant Setpoint, Modbus Wired Header Temp Sensor
Step 2: OPTION 2 CONFIGURATION
On All Boilers:
1. Go to: Main Menu → Advanced Setup → BST Cascade → Cascade Configuration:
• Set the Unit Mode parameter to BST Client.
2. Go to: Main Menu → Advanced Setup → BST Cascade → Cascade Communication:
• Set the Unit Address parameter to the communication address of the unit.
On the BST Manager only:
1. Go to Main Menu → Advanced Setup → BST Cascade, set the Parameters to the Values
in each menu in the table below.
Application
Configuration
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.