EasyManua.ls Logo

Watts AERCO Benchmark OMM-0136 - Page 94

Watts AERCO Benchmark OMM-0136
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7 BOILER SEQUENCING TECHNOLOGY
OMM-0137_E • GF-211 12/13/2019 Technical Support (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 94 of 153
OPTION 3 Instructions: Outdoor Reset, Direct Wired Header Temp Sensor & Outdoor Temp
Sensor
Step 3 OPTION 3 CONFIGURATION
On All Boiler:
1. Go to: Main Menu Advanced Setup BST Cascade Cascade Configuration:
Set the Unit Mode parameter to BST Client.
2. Go to: Main Menu Advanced Setup BST Cascade Cascade Communication:
Set the Unit Address parameter to the communication address of the unit.
On the BST Manager only:
1. Go to Main Menu Advanced Setup BST Cascade, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Unit Mode
BST Manager
Hdr Temp Sensor
Header Temp
Application
Configuration
Application
Space Heating
SH Operating Mode
Outdoor Reset
Outdoor Temp Sensor
Outdoor Sensor
Plant Setpoint
Header temperature required for the cascade
Cascade
Communication
Min Address
The minimum unit address in the cascade
Max Address
The maximum unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.

Table of Contents

Related product manuals