Modulex EXT Commercial Series Boilers User Manual
CHAPTER 6: Operation of the E8 Controller
OMM-0095_0H AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 107 of 144
GF-139 Phone: 800-526-0288 09/15/2017
A Second DHW Storage Tank 6.10.1.3
(Only After Function Selection)
Offers the possibility to use one of the heating zones for the preparation of a second DHW
storage tank.
EXPERT menu ⇒ Heating circuit I/II ⇒ HC FUNC. “03”
Temperature Setting For Second DHW Storage Tank 6.10.1.4
USER menu ⇒ Heating circuit / II ⇒ T- HW
Swimming Pool 6.10.1.5
Offers the possibility to use one of the heating zones for the heating of a swimming pool.
EXPERT menu ⇒ Heating circuit I/II ⇒ HC FUNC “02”
Swimming Pool Temperature Setting 6.10.1.6
(Only After Function Selection)
USER menu ⇒ Heating circuit I / II ⇒ T- POOL 1 / 2 / 3
Screed Dry Program (For Floor Heating Installation) 6.10.1.7
A program setting for drying the screed.
EXPERT menu ⇒ Installation ⇒ SCREED “01”
Temperature Setting For Screed Program 6.10.1.8
USER menu ⇒ Heating circuit I / II
Signal 0 – 10 V 6.10.1.9
Uses a 0-10 V input to control fire rate via an external control..
EXPERT menu ⇒ Solar/MF ⇒ FUNC. F15 “01”
Slope And Temperature Setting with 0 – 10 V Signal 6.10.1.10
See Table 6-7 for values.
EXPERT menu ⇒ Installation ⇒ TENS SLOPE (0 to 11)
EXPERT menu ⇒ Installation ⇒ SLOPE 11 – XX (freely settable)