7.1.3 BMM (Burner Management Module) Fault Codes
The table below lists the fault codes and troubleshooting tips associated with the BMM.
TABLE 7-4: BMM Fault Codes
CODE DESCRIPTION EFFECT CORRECTION RESET
E 1
Thermostat
activated.
turned OFF and
pump ON at
maximum speed.
Check flow sensor thermal
connection to boiler.
reset switch
when
temperature goes
E 2
pressure.
turned OFF.
Check gas pressure or gas
pressure switch.
when gas
pressure switch
E 4
detected at
lockout.
combustion.
reset switch or
E 5
run.
wiring.
reset switch or
E 6
temperature.
Flow sensor
temperature >
turned OFF and
pump ON at
maximum speed.
system pump
when Flow
sensor < 176°F.
E 10
Contact factory for new
BMM.
MANUAL - cycle
the power.
E 11
detected before
ignition.
inhibited.
Disconnect flame rod wire
from BMM. If problem
goes away, change flame
rod and/or wire. If problem
does not go away, change
reset switch or
cycle power.
E 12
Check flow sensor or
wiring.
E 13
Aux sensor fault.
operate from the
Flow sensor
without the Aux
Check aux sensor or
wiring.
AUTOMATIC