TABLE 7-4: BMM Fault Codes
CODE DESCRIPTION EFFECT CORRECTION RESET
E 14
Check return sensor or
wiring.
E 15
temperature
protection.
Flow
temperature -
Return
Temperature >
Water Δ-Temp
Protection +
turned OFF
and Pump
ON at
maximum
speed.
installation.
Δ-temperature < Water
Δ-Temp Protection.
E 16
frozen. Flow
sensor
temperature is
inhibited.
Pump runs for
5 min at max
Carefully defrost boiler.
flow sensor is greater
than 41°F.
E 20
detected after
burner is OFF.
inhibited.
Disconnect gas valve wire
from BMM. If failure goes
away, check wiring or
change BMM. If failure
remains, check or change
switch or cycle power.
E 22
burner after fan
started for 30
seconds.
after 60
second delay
and failure
remains until
a successful
burner
operation.
supply voltage and fan
wiring. If OK, try another
fan. If still not working,
change the BMM.
If fan is not stopped, check
the exhaust gas outlet for
blockage. If OK, check the
air pressure switch wiring.
If still not working, try
another air pressure
switch. If still not working,
E 23
pressure
switch doesn't
switch off.
inhibited.
Disconnect the air proving
switch. If problem goes
away, install a new switch.
If not, check the wiring. If
wiring is OK, change BMM.