EasyManua.ls Logo

Watts Aerco Modulex MLX EXT 1530 - Page 69

Watts Aerco Modulex MLX EXT 1530
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modulex EXT Commercial Series Boilers User Manual
CHAPTER 4: Installation Instructions
OMM-0095_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 69 of 144
GF-139 Phone: 800-526-0288 09/15/2017
TABLE 4-6: EXT Pressure, CO
2
and O
2
Level Calibration Tables
EXT 2677 / 2600
Gas
Type
Supply
Pressure
Wc (kPa)
CO
2
Level O
2
Level Fan Speed
Ǿ Mixer
Injectors
Ǿ in.
(mm)
Min. Gas
Consumption
ft
3
/hr (m
3
/hr)
Max. Gas
Consumption
ft
3
/hr (m
3
/hr)
Start
Output
% IG
(%)
Min.
(%)
Max.
(%)
Min.
(%)
Max.
Min.
(FL)
Max.
(FH)
NOMINAL ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 26 84 0.35 (9) 79.8 (2.26) 2565 (72.6) 50
Propane
11 (2.74) 10 11 1.3 3.1 26 82 0.35 (9) 32.4 (0.92) 1042 (29.5) 50
HIGH ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 28 100 0.35 (9) 79.8 (2.26) 2565 (72.5) 50
Propane
11 (2.74) 10.2 10.6 1.3 3.1 26 76 0.35 (9) 32.4 (0.92) 938 (26.6) 50
EXT 3060 / 3000
Gas
Type
Supply
Pressure
Wc (kPa)
CO
2
Level O
2
Level Fan Speed
Ǿ Mixer
Injectors
Ǿ in.
(mm)
Min. Gas
Consumption
ft
3
/hr (m
3
/hr)
Max. Gas
Consumption
ft
3
/hr (m
3
/hr)
Start
Output
% IG
(%)
Min.
(%)
Max.
(%)
Min.
(%)
Max.
Min.
(FL)
Max.
(FH)
NOMINAL ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 26 84 0.35 (9) 79.8 (2.26) 2932 (83.0) 50
Propane
11 (2.74) 10 11 1.3 3.1 26 82 0.35 (9) 32.4 (0.92) 1191 (33.7) 50
HIGH ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 28 100 0.35 (9) 79.8 (2.26) 2639 (82.9) 50
Propane
11 (2.74) 10.2 10.6 1.3 3.1 26 76 0.35 (9) 32.4 (0.92) 1072 (30.3) 50
NOTE:
Check the O
2
levels often, especially at low flow rates.
For high altitude installations, consult document number C302.6 (MLX EXT Alt Derate).