Modulex EXT Commercial Series Boilers User Manual
CHAPTER 4: Installation Instructions
OMM-0095_0H AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 69 of 144
GF-139 Phone: 800-526-0288 09/15/2017
TABLE 4-6: EXT Pressure, CO
2
and O
2
Level Calibration Tables
Gas
Type
Supply
Pressure
Wc (kPa)
CO
2
Level O
2
Level Fan Speed
Ǿ Mixer
Ǿ in.
(mm)
Min. Gas
Consumption
ft
3
/hr (m
3
/hr)
Max. Gas
ft
3
/hr (m
3
/hr)
Start
Output
% IG
(%)
Min.
(%)
Max.
(%)
Min.
(%)
Max.
(FL)
Max.
(FH)
NOMINAL ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 26 84 0.35 (9) 79.8 (2.26) 2565 (72.6) 50
Propane
11 (2.74) 10 11 1.3 3.1 26 82 0.35 (9) 32.4 (0.92) 1042 (29.5) 50
HIGH ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 28 100 0.35 (9) 79.8 (2.26) 2565 (72.5) 50
Propane
11 (2.74) 10.2 10.6 1.3 3.1 26 76 0.35 (9) 32.4 (0.92) 938 (26.6) 50
Gas
Type
Supply
Pressure
Wc (kPa)
CO
2
Level O
2
Level Fan Speed
Ǿ Mixer
Ǿ in.
(mm)
Min. Gas
Consumption
ft
3
/hr (m
3
/hr)
Max. Gas
ft
3
/hr (m
3
/hr)
Start
Output
% IG
(%)
Min.
(%)
Max.
(%)
Min.
(%)
Max.
(FL)
Max.
(FH)
NOMINAL ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 26 84 0.35 (9) 79.8 (2.26) 2932 (83.0) 50
Propane
11 (2.74) 10 11 1.3 3.1 26 82 0.35 (9) 32.4 (0.92) 1191 (33.7) 50
HIGH ALTITUDE
Natural
7 (1.74) 8.5 10 3.1 5.8 28 100 0.35 (9) 79.8 (2.26) 2639 (82.9) 50
Propane
11 (2.74) 10.2 10.6 1.3 3.1 26 76 0.35 (9) 32.4 (0.92) 1072 (30.3) 50
NOTE:
Check the O
2
levels often, especially at low flow rates.
For high altitude installations, consult document number C302.6 (MLX EXT Alt Derate).