SmartPlate Installation, Operation & Maintenance Manual
CHAPTER 8 CORRECTIVE MAINTENANCE
OMM-0069_0H SP-100 1/30/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 71 of 134
CLOSING HEAT EXCHANGER Instructions
Figure 8-13. Closing the Heat Exchanger
6. Brush the threads of the bolts clean, using a steel wire brush.
7. Lubricate the threads with a thin layer of grease.
8. Place the bolts in position and tighten the plate pack using diagonally opposite bolt pairs,
(the opposite of the opening procedure in section 8.7.1, step 10) until the plate pack length
is reduced to ±1% of dimension "A" in the channel plate assembly instructions supplied
with unit. During tightening. The pressure plate must not be out-of-parallel to the frame
plate by more than 3/8" in the horizontal plane and 1" in the vertical plane. See Figure 8-
14.