SECTION 13: DISCHARGE HEADS AND SPLASH PLATES
33
13.2 Splash Plate Installation
The splash plate is designed to hang directly from a horizontal air handler with a bottom discharge. Before
the splash plate can be installed on the air handler, first drill four holes in the air handler floor. These holes to
be centered over the entire blower discharge opening. These holes should be approximately 5/8" (15.9 mm)
in diameter to accommodate 1/2" hanger rods (supplied by others). These holes should be located as shown
in the diagram on Page 34, Figure 17.
To attach all of the hanger rods to the splash plate, start by threading a flanged nut onto each hanger rod.
Then, slip each hanger rod down through a hole located in each corner of the splash plate. Next, feed a
flanged nut onto the rod below the splash plate See Page 33, Figure 16. The hanger rods should be attached
to the air handler in the same manner as the splash plate, with a flanged nut on both sides of the air handler
floor. Adjusting the nuts will level the splash plate. Torque hardware after leveling.
FIGURE 16: Splash Plate
Model A B C
(min)
C
(max)
XT-112 (in)
(cm)
25.5
(64.8)
27.6
(70.1)
15.0
(38.1)
20.0
(50.8)
XT-115 (in)
(cm)
37.0
(94.0)
35.1
(89.2)
18.0
(47.5)
27.0
(68.6)
XT-118 (in)
(cm)
39.8
(101.1)
39.6
(100.6)
18.0
(47.5)
27.0
(68.6)
XT-125 (in)
(cm)
43.3
(110.0)
43.6
(110.7)
25.0
(63.5)
38.0
(96.5)
XT-130 (in)
(cm)
48.7
(123.7)
48.7
(123.7)
30.0
(76.2)
45.0
(114.3
)