EasyManua.ls Logo

Weidmüller UC20-WL2000-AC - 5.3 UC20-SL2000-EC

Default Icon
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Detaildescriptionofcontrollers | UC20-SL2000-EC
31Manual u-control2604080000/03/08.2020
5.3 UC20-SL2000-EC
Up to 64 active u-remote modules can be connected via the
u-remote system bus to the UC20-SL2000-EC controller. The
controller has two Ethernet connections for integration into
the existing network architecture or HMI connections.
The controller can be congured as a EtherCAT master.
The u-control station can be congured and parametrised
and controlling applications can be programmed using the
engineering tool u-create studio (according to IEC61131-3,
additional programming languages: C and C++)
The station’s main power supply is integrated into the con-
troller. Power is supplied via two 4-pole connectors, separat-
ed into the input and output current paths.
Controller UC20-SL2000-EC (Order No. 2674520000)
Status indicators
PWR
SF
BF
MT
AC
1
2
3
4
1
2
3
4
RUN/STOP
L/A X1
L/A X2
3
4
X1
X2
LEDstatusindicatorsUC20-SL2000-EC,forerrormessagesseeChapter12
PWR Power LED green: supply voltage present, rmware is
running
SF System failure red: system bus failure
BF Bus failure red: eld bus failure
MT Maintenance yellow: communication error with module
RUN Controller status green: application running
greenashing: application stopped
yellow: operating system running
yellowashing: system update running
red: serious system failure
L/A X1 Connection/
activity
green: connection of controller connection 1
with an additional eld device
green/yellowashing: data being ex-
changed on connection1
L/A X2 Connection/
activity
green: connection of controller connection 2
with an additional eld device
green/yellowashing: data being ex-
changed on connection2

Table of Contents

Related product manuals