EasyManua.ls Logo

Weidmüller UC20-WL2000-AC - 6.5 Inserting the SD card; 6.6 Insulation test

Default Icon
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 2604080000/03/08.2020Manual u-control
6 Installation | Inserting the SD card
6.5 Inserting the SD card
Unlock the connector frame and open it as far as possible
(at least to an angle of 90°).
Opening the connector frame
Insert the SD card as shown.
Inserting the SD card
Close the connector frame.
6.6 Insulation test
Insulation tests on the u-control station have to be done ac-
cording to the national regulations, in any case necessarily
before each commissioning.
ATTENTION
The product can be destroyed by too
high test voltage!
Please note during insulation test:
within one channel the test voltage
between 24V and GND must not exceed
28,8V!
1)
A maximum test voltage of 500V can be
applied tho all other connection points.
Up to 4000V can be applied to the mod-
ules UR20-4RO-SSR-255 and
UR20-4RO-CO-255:
between the four channels
between one channel and the system
voltage.
1) We recommend to short-circuit 24V and GND on all pow-
er supply connectors (controller, power-feed modules, safe
power-feed modules and PLC-modules).