6.5.29 Set switch on optimisation
This parameter is only displayed, if room or weather compensation has been activated
in level Type of control#1 (see Ch. 6.5.8).
To ensure the room setpoint temperature has been reached at the beginning of normal
operation (heating program), the switch on time is preset. The parameter
On Opti
limits the maximum time of the pre-setting. At
Curr
the current pre-set time calculated
is displayed.
Room dependent variation (pre-setting based on the actual room temperature)
Setting parameter
318 Room
or
External/Room
(see Ch. 6.5.8).
The optimisation function is reset to the maximum value:
after resetting of the WCM-FS,
after resetting of parameter via function key 2,
after changing parameter heating circuit type (P316).
Weather dependent variation (pre-setting based on the external temperature)
Setting parameter
318 External
(see Ch. 6.5.8).
Setting range
Off
00:15
04:00 h
Activate heating engineer level (see Ch. 6.5).
Press function key
Heating circuit
.
Press function key
Control behaviour
.
Menu
Control behaviour
is displayed.
Press function key
On Opti
.
Parameter
On Opti
is displayed.
Set value using the dial knob and save with function key
OK
.
01
Control behaviour
Reduced oper. Setback
Frost limit Off
On Opti
End
-
+
On Opti 503
End
Reset
Standard
OK
--;00:15 - 04:00
Act ----
Max 02:00h
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
76-106

Table of Contents

Other manuals for Weishaupt WCM-FS 2.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Weishaupt WCM-FS 2.0 and is the answer not in the manual?

Weishaupt WCM-FS 2.0 Specifications

General IconGeneral
BrandWeishaupt
ModelWCM-FS 2.0
CategoryControl Systems
LanguageEnglish

Related product manuals