6.5.41 Activate circulation during Legionella protection function
In conjunction with a WTC 25-A vers. C this parameter is not displayed.
Setting range
On Circulation is active during the entire disinfection process. If the
pipework is long this setting leads to high heat loss.
Off Operation of the circulation pump at the end of the Legionella
protection function for the duration set in parameter 609
(see Ch. 6.5.42).
Activate heating engineer level (see Ch. 6.5).
Press function key
DHW
.
Menu
DHW
is displayed.
Press function key
Circ during Legio
.
Parameter
Circ during Legio
is displayed.
Set
ON
using the dial knob and save with function key
OK
.
-
+
Circ during Legio 608
End
Standard
OK
Off
Off - On
02
DHW
Legio time 22.00
Circ during Legio Off
Circ time 03:00min
End
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
89-106

Table of Contents

Other manuals for Weishaupt WCM-FS 2.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Weishaupt WCM-FS 2.0 and is the answer not in the manual?

Weishaupt WCM-FS 2.0 Specifications

General IconGeneral
BrandWeishaupt
ModelWCM-FS 2.0
CategoryControl Systems
LanguageEnglish

Related product manuals