Installation and operating instruction
Gas burner WG20…/1-C LN
10 Troubleshooting
83240802 1/2020-01 La
69-96
The following faults must only be rectified by qualified personnel:
Fault codes Fault Cause Rectification
Flashing 7 times
Flame failure during opera-
tion
Flame signal insufficient Burner setting incorrect Check burner setting
Check flame signal
Ionisation electrode soiled Clean ionisation elec-
trode
Ionisation electrode set in-
correctly
Set ionisation electrode
[ch.9.5]
Ionisation electrode defect-
ive
Check the ionisation
electrode, replace if ne-
cessary
Flashing 8 times
Gas pressure switch fault
Gas pressure switch does
not react
Gas pressure switch set in-
correctly
Set gas pressure switch
[ch.7.3.1]
Gas pressure switch de-
fective
Check gas pressure
switch, if necessary re-
place
Flashing 10 times
Combustion manager fault
Burner does not start Parameters have been
changed
Reset burner [ch.10.1.2]
Combustion manager de-
fective
Reset burner [ch.10.1.2],
if fault reoccurs replace
combustion manager

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Weishaupt WG20-/1-C LN Series and is the answer not in the manual?

Weishaupt WG20-/1-C LN Series Specifications

General IconGeneral
BrandWeishaupt
ModelWG20-/1-C LN Series
CategoryIndoor Fireplace
LanguageEnglish

Related product manuals