19WIKA operating instructions pressure transmitter, model IS-3
MM/YYYY country code based on 14095850.02 12/2014 EN/CN
EN
Permissibletemperaturesforoperationinaccordancewiththedatasheetspecications(forignition
protection Ex i)
The selected temperature range of the particular pressure transmitter can be found on the delivery note.
Medium
Standard -20 ... +80 °C
Option 1 -20 ... +150 °C (only for ush process connections and measuring ranges ≤ 600 bar)
Option 2 -40 ... +150 °C (only for process connections with pressure channel and measuring ranges ≤ 400 bar)
Option 3 -40 ... +200 °C (only for process connections with pressure channel and measuring ranges ≤ 400 bar)
Oxygen -20 ... +60 °C
Ambient: -20 ... +80 °C
- Cable outlet IP 68 (continuous use in the medium), PUR cable: -15 ... +70 °C
- Cable outlet IP 68 (continuous use in the medium), FEP cable: -15 ... +80 °C
Storage: -20 ... +80 °C
Permissibletemperaturerangesforoperationinaccordancewiththedatasheetspecications(forignition
protection Ex nA and Ex tc)
Medium:
-15 ... +70 °C (with oxygen -15 ... +60 °C)
Ambient:
-15 ... +70 °C
Storage:
-15 ... +70 °C
3.Specications

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WIKA IS-3 and is the answer not in the manual?

WIKA IS-3 Specifications

General IconGeneral
Output Signal4 ... 20 mA, 2-wire
Power Supply10 ... 30 VDC
MaterialStainless steel
Accuracy≤ ±0.5 % of span
Temperature Range-20 ... +85 °C
Ingress ProtectionIP65
Long-term stability±0.2 % FS per year
Process ConnectionG 1/4, G 1/2, 1/4" NPT, 1/2" NPT
Electrical ConnectionM12 x 1