24 WILO SE 05/2017
EN
English
1. General
See start of document.
2. Safety
See start of document.
3. Transport and interim storage
When you receive the equipment, check that it
has not been damaged during transport. If you
notice any defects, take all necessary measures
with the carrier in the time provided.
WARNING! The environment may cause damage.
If the equipment delivered must be installed
subsequently, store it in a dry place and protect it
from shock and any other effects (humidity, frost,
etc.).
Transport and storage temperatures: -30 °C to
+60 °C.
Handle the product with care so as not to dam-
age it prior to installation.
4. Intended use
The Wilo-Plavis ...-C product is designed for pump-
ing condensates emitted by the following systems:
Boiler
Air-conditioning system
Cooling and refrigeration system
Airdehumidication
The product is suitable for pumping collected
condensates that cannot be sent towards the
drains or drained from the building by the natural
slope.
DANGER! Risk of explosion!
Donotusethispumptoconveyammableor
explosive liquids.
WARNING!
The condensates from boilers are aggressive due
to their acidity. Always wear gloves and protec-
tive glasses for maintenance work.
The condensates from boilers must be processed
(potentially neutralised) in compliance with the
local regulations before being sent to the drains.
5. Product information
5.2 Scope of delivery
Wilo-Plavis ...-C
+ 2 fastening screws Ø 4
+ 5 m drainage pipe Ø 8 x 11 (based on the model)
+ Bag with granules for pH neutralisation (Plavis
015-C)
+ Installation and operating instructions
6. Description and function
6.1 Description (g.3,4)
1 Pump set
2 Tankoverowsafetylevel(basedonthemodel)
3 Tank cover
4 Hatch (based on the model)
5 Plug adapter (based on the model)
6 Power supply
7 Alarm cable (based on the model)
8 Non-return valve
9 Tank
10 Granulated chamber wall for neutralisation
11 Low-level probes
12 High-level probes
13 Alarm probe (based on the model)
14 Alarm indicator (based on the model)
15 Alarm switch (based on the model)
A Suction
B Drainage
6.2 Function
The condensates are collected in the tank
The level of liquid is automatically controlled by
the electronic card
The pump starts when the liquid level reaches
the high-level probe, and stops when the liquid
level has descended to the low-level probe
The condensates are drained away through the
drainage piping
The product is equipped with an alarm probe in
case of defect (based on the model). This alarm
probe activates the alarm relay that may be con-
nected via the alarm cable
5.1 Technical data
Designation Wilo-Plavis 011-C Wilo-Plavis 013-C Wilo-Plavis 015-C
Supply voltage 1 ~ 100-240 Vac
Frequency 50/60 Hz
Supply cable 1.5 m
Alarm cable - 1.5 m
Power consumption < 20 W
Rated current 0,2 A
Protection class IP X4
Ambient temperature from + 5 °C to + 40 °C
Alarm relay contact - 230 V rms 1A
Delivery head Max. 4 m
Admissibleuid pH > 2.5
Admissibleuidtemperature from + 5 °C to + 60 °C
Sound-pressure level < 40 dBA at 1 m
Dimensions (L x W) 152 x 116 mm 210 x 123 mm 275 x 129 mm
Tank volume 0.7 l 1.1 l 1.,6 l
* with granules
* 0,8 l
Net weight (± 10 %) 700 gr 750 gr 1 000 gr * 1 800 gr