Installation and operating instructions Wilo-Star-Z/-ZD 29
English
1)
The values apply up to 300 m above sea level; addition for higher locations:
0.01 bar/100 m increase in altitude. To prevent cavitation noises, be sure
to maintain the minimum inlet pressure at the suction port of the pump.
2)
For Star-ZD double pumps, a switchgear is required in addition for time-dependent
main/standby or parallel/peak-load operation.
5.3 Scope of delivery
Complete circulation pump
•2 flat gaskets
Installation and operating instructions
5.4 Accessories
Accessories must be ordered separately:
Thermal insulation shell (for single pumps only)
Screwed connections
•S1R-h plug-in module
See catalogue for a detailed list
5.2 Technical data
Connection voltage 1 ~ 230 V ±10%, 50 Hz
1 ~ 220/230 V ±6%, 60 Hz
Protection class IP See rating plate
Motor speed See rating plate
Water temperature at
max. ambient temperature +40 °C
+2 °C to +65 °C
Max. ambient temperature +40 °C
Max. operating pressure 10 bar (1000 kPa)
Minimum inlet pressure
1)
at +40 °C/+65 °C
0.05 bar/0.2 bar
(5 kPa/20 kPa)
Variable speed control
2)
3 stages