Installation and operating instructions Wilo-Star-Z/-ZD 35
English
WARNING! Risk of injury!
Depending on the temperature of the fluid and system pres-
sure, when the venting screw is opened, hot liquid or gaseous
fluid may escape or shoot out at high pressure.
Escaping fluid can cause scalding!
Undo the venting screw carefully with a suitable screwdriver
and unscrew it completely (fig. 8).
Carefully push back the pump shaft with a screwdriver several
times.
Protect electrical parts from any escaping water.
Switch on the pump.
Note. The pump may jam if the vent screw is undone, depend-
ing on the operating pressure level
Screw the venting screw back in again after 15 to 30 seconds.
Open the shut-off device again.
8.2 Adjusting
Speed
The speed is adjusted by means of the rotary knob on the
terminal box (fig. 7).
Note. If on a double pump both the individual pumps are in
operation at the same time, the selected speeds must be
identical for both pumps.
9Maintenance
DANGER! Risk of fatal injury!
There is a risk of fatal injury from electric shock when work-
ing on electrical equipment.
The pump should be electrically isolated and secured against
unauthorised switch-on for any maintenance or repair work.
Any damage to the connection cable should only ever be
eradicated by a qualified electrician.