en Faults, causes and remedies
42 WILO SE 2017-06
Fault: Pump starts, duty point is not reached
1. Inlet clogged.
Check the inlet and remove clogging.
2. Slide valves on the pressure side closed.
Open all gate valves completely.
3. Hydraulics jammed.
Clean the hydraulics.
4. Incorrect direction of rotation.
Have the connection corrected by a qualified electrician.
5. Air cushion in the pipe system.
Vent the pipe system.
If air cushions occur frequently: Locate and prevent the air intake, if required
install ventilation systems at specified locations.
6. Pump pumping against excessive pressure.
Open all gate valves on the pressure side completely.
Check the impeller shape, use other impeller shapes if required. Contact cus-
tomer service.
7. Signs of wear on the hydraulics.
Have the components (impeller, suction port, pump housing) checked and re-
placed by customer service.
8. Pipe system on the pressure side or pressure hose clogged.
Remove clogging and replace the damaged components if necessary.
9. Strongly gassing fluid.
Contact customer service.
10.There are only two phases at the connection.
Have the connection checked and corrected by a qualified electrician.
11.Excessive decrease in the fill level during operation.
Check supply/capacity of the system.
Have the switching points of the level control checked and adjusted if neces-
sary.
Fault: The pump does not run smoothly and is noisy
1. Improper duty point.
Check the pump configuration and the duty point, contact customer service.
2. Hydraulics jammed.
Clean the hydraulics.
3. Strongly gassing fluid.
Contact customer service.
4. There are only two phases at the connection.
Have the connection checked and corrected by a qualified electrician.
5. Incorrect direction of rotation.
Have the connection corrected by a qualified electrician.
6. Signs of wear on the hydraulics.
Have the components (impeller, suction port, pump housing) checked and re-
placed by customer service.
7. Motor bearings have worn.
Inform customer service; send the pump back to the factory for overhauling.
8. Pump is installed under tension.
Check installation, install rubber compensators if necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Wilo-EMU FA + FK 17.1 and is the answer not in the manual?

Wilo Wilo-EMU FA + FK 17.1 Specifications

General IconGeneral
BrandWilo
ModelWilo-EMU FA + FK 17.1
CategoryWater Pump
LanguageEnglish

Related product manuals