34 Wilo SE 08/2017
en
iPWM 2 mode:
In iPWM 2 mode, the pump speed is controlled according
to the PWM input signal.
Behaviour in the event of a cable break:
If the signal cable is separated from the pump, e.g. due
to a cable break, the pump stops.
PWM signal input [%]
0-7: Pump stops (standby)
7-15: Pump runs at minimum speed (operation)
12-15: Pump runs at minimum speed (starting)
15-95: The speed of the pump increases linearly from
n
min
to n
max
> 95: Pump runs at maximum speed
Venting
The pump venting function is activated by pressing and
holding the operating button (for 3 seconds) and auto-
matically vents the pump.
The heating system is not vented.
Manual restart
A manual restart is initiated by pressing and holding the
operating button
(for 5 second) and unblocks the pump if required
(e.g. after long standstill period in summer).
Lock/unlock the
button
The key lock is activated by pressing and holding the
operating button (for 8 seconds) and locks the pump’s
current settings. It protects against undesired or unau-
thorised adjustment of the pump.
4 Intended use
High-efficiency circulators in the Wilo-Para series are
exclusively intended for circulating fluids in hot-water
heating systems and similar systems with constantly
changing volume flows.
Permitted fluids:
Heating water according to VDI 2035
(CH: SWKI BT 102-01).
Water-glycol mixtures* with a maximum of 50 % glycol.
max
min
0 7 12 15
95 100
PWM
%
n
¹/min