6.2 Electrical connection
The electrical connection may only be carried out by a
qualified electrician.
Preparation
The current type and voltage must agree with the
specifications on the rating plate (6).
Maximum back-up fuse: 10 A, slow-blow.
Only operate the pump with sinusoidal AC voltage.
Note the switching frequency:
- On/off switching operations via mains voltage
100/24 h.
- 20/h for a switching frequency of 1 min.
between switching on/off via mains voltage.
DANGER!
Risk of fatal injury from electrical voltage!
Immediate risk of fatal injury if live components are
touched.
Before commencing work, switch off the power sup-
ply and secure it from being switched on again.
Never open the control module (6) and never remove
control elements.
CAUTION!
Pulsed mains voltage can cause damage to electronic
components.
Never operate the pump with phase angle control.
When switching the pump on or off using an external
control unit, deactivate any voltage pulse (e.g. phase
angle control).
For applications where it is not clear whether the
pump is operated with pulsed voltage, get the con-
trol/system manufacturer to confirm that the pump
is operated with sinusoidal AC voltage.
Switching the pump on/off via triacs/solid-state
relays must be examined on a case-by-case basis.