40 Wilo SE 08/2017
en
The electrical connection must be made via a fixed
connecting cable equipped with a connector device or
an all-pole switch with a contact opening width of at
least 3 mm (VDE 0700/Part 1).
Use a connecting cable with sufficient outer diameter
(e.g. H05VV-F3G1.5) to protect against leaking water
and to ensure strain relief on the threaded cable con-
nection.
Use a heat-resistant connecting cable where fluid
temperatures exceed 90 °C.
Ensure that the connecting cable does not make con-
tact with either the pipes or the pump.
Mains cable
connection
Installing the mains connection cable (Fig. 3):
1. Standard: 3-core coated cable with brass ferrules
2. Optional: Mains cable with 3-pin connection plug
3. Optional: Wilo-Connector cable (Fig. 3, item b)
Cable assignment:
1 yellow/green: PE (
;)
2 blue: N
3 brown: L
Press down the locking button of the 3-pin pump
plug and connect the plug to the plug connection (12)
of the control module until it snaps into place (Fig. 4).
Wilo-Connector
connection
Installing Wilo-Connector
Disconnect the connecting cable from the power
supply.
Observe terminal assignment (
; (PE), N, L ).
Connect and install the Wilo-Connector (Fig. 5a
to 5e).
Connecting the pump
Earth the pump.
Connect the Wilo-Connector to the connection cable
until it snaps into place (Fig. 5f).
Removing the Wilo-Connector
Disconnect the connecting cable from the power
supply.