EasyManua.ls Logo

Witt GP 41 - Adaptation to Plant Requirements

Witt GP 41
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- Applications - 26
RECIRCULATION RATES AND PUMP CAPACITY
Recirculation factor Recirculation flow in m³/hr per 100 kW*
Refrigerant CO
2
NH
3
R22 CO
2
NH
3
R22
Air Cooler 1,2 – 2,0
3 - 4 2 - 3 1,4 – 2,4 1,3 – 1,8 2,8 – 4,3
Plate Freezer
5 - 10 7 - 10 5 - 10 6 - 12 3 – 4,5 6,5 - 13
Liquid Chiller
1,2 – 1,5 1,2 – 1,5 1,2 – 1,5 1,4 – 1,6 0,6 1,7
*) including re-circulation rate
5.4 ADAPTATION TO PLANT REQUIREMENTS
Fig. 5 shows different plant operating conditions. The delivery head H is shown in relation to
the required plant capacity Q.
Performance curve characteristics of the refrigerant pump are shown in fig 5A. The different
points W mark the varying plant conditions that may occur during operation.
If the required liquid flow does not correspond with the available pump capacity then the liquid
flow to the sys-tem can be adjusted as follows:
pump capacity too large:
switch off a pump
open a liquid bypass valve, fig. 5B
speed control of the pump, fig 5C
pump capacity too small:
switch on an extra pump, fig 5D
install a larger pump
Fig. 5, A-D
V
1
+V
2
≠ 2 x V
1

Related product manuals