  • E
    Eric HeathSep 9, 2025
    What to do if my Wolf MGK-130 detects a fault with gas valve "1"?
    • S
      Steven LucasSep 9, 2025
      If a flame is detected for 15 seconds after burner operation, even though gas valve 1 has received a shutdown command, replace the gas combination valve.
  • M
    Mary CarrSep 8, 2025
    What to do if my Wolf Boiler's return sensor is faulty?
    • T
      Tammy EdwardsSep 8, 2025
      If the return temperature sensor or lead is faulty, check the lead and replace the return sensor.
  • L
    lhoustonAug 22, 2025
    What to do if the Wolf MGK-130 has no flame?
    • L
      Laura ValdezAug 22, 2025
      If no flame builds during burner start, check the gas supply line and open the gas valve if needed. Also, check the ignition electrode and ignition cable. Press the reset button.
  • D
    Daniel ThompsonSep 5, 2025
    What to do if my Wolf MGK-130's cylinder sensor is faulty?
    • A
      Ariel MooreSep 5, 2025
      If the DHW temperature sensor or lead is faulty, check the sensor and lead.
  • S
    Stephanie WilliamsSep 4, 2025
    What to do if my Wolf MGK-130 Boiler's gas fan does not stop?
    • J
      John WalkerSep 4, 2025
      If the gas fan does not stop, check the gas fan supply cable and the gas fan; press the reset button.
  • P
    Paul McgeeSep 2, 2025
    What to do if my Wolf Boiler's gas fan does not reach the ignition speed?
    • H
      hardyemilySep 3, 2025
      If the gas fan does not reach the ignition speed, check the gas fan supply cable and the gas fan; press the reset button.
  • M
    Melissa McdonaldSep 1, 2025
    What to do if my Wolf MGK-130 Boiler's gas fan does not reach the required pre-purging speed?
    • C
      Courtney LewisSep 1, 2025
      If the gas fan does not reach the required pre-purging speed, check the gas fan supply cable and the gas fan; press the reset button.
  • A
    Ann Friedman MDAug 31, 2025
    What to do if the Wolf MGK-130 shows a faulty flow sensor or gas pressure is too low?
    • T
      Terry StoneAug 31, 2025
      If the flow temperature sensor or lead is faulty, or the gas pressure is lower than the value set at the gas pressure switch (only displayed after 15 min), check the lead, the flow sensor, the gas pressure, and the gas pressure switch settings.
  • A
    amandagardnerAug 30, 2025
    What to do if my Wolf MGK-130 Boiler has a flame pretence?
    • J
      Joseph Cox MDAug 30, 2025
      If a flame is recognized before the burner starts, press the reset button.
  • R
    Ryan BarkerAug 29, 2025
    What to do if my Wolf Boiler shows TW excess temperature?
    • L
      Lisa SmithAug 29, 2025
      If the flow/return temperature has exceeded the limit for the TW shutdown temperature, check the system pressure, vent the system, and set the pump to stage 2 or 3.