Questions and Answers

  • M
    matthew27Aug 27, 2025
    Why is my Wolf MGK-130 Boiler's LED constantly red?
    • H
      Hannah CastroAug 27, 2025
      If the LED is constantly red, it might be because the ionization cable is shorted out or the ionization electrode is earthed (casing). Check the ionization cable and the position of the electrode to the burner. Press the reset button.
  • B
    Benjamin OnealAug 27, 2025
    What to do if my Wolf MGK-130 Boiler shows TBA excess temperature and overpressure in the flue gas system?
    • E
      Elizabeth FullerAug 27, 2025
      If the flue gas temperature has exceeded the limit for the TBA shutdown temperature, the flue gas system is blocked, or the ventilation air is blocked, clean the heat exchanger, check the flue gas system, and check the ventilation air system.
  • J
    Jeffrey CurtisAug 25, 2025
    What to do if my Wolf MGK-130 Boiler shows TBV excess temperature and water pressure is too low?
    • C
      Christine HillAug 26, 2025
      If the flow temperature has exceeded the limit for the TBV shutdown temperature, or the condensate lifting pump has a fault, or the water pressure switch switches off at a pressure less than 1.0 bar, check the system pressure, the heating circuit pump and vent the system. Press the reset button. Check the condensate pump and increase system pressure.
  • P
    Philip MaysAug 25, 2025
    What to do if the Wolf MGK-130's flame fails during operation?
    • J
      James PearsonAug 25, 2025
      If the flame fails within 15 seconds after flame detection, check the CO values and the ionization electrode and its cable. Press the reset button.