16 3043757_201801
Installation Tips /
Commissioning / Servicing
The buffer must be installed in such a way that it can be emptied as completely as
possible. The SPU-1-200 tank is equipped with a boiler ll and drain valve.
Warning: When emptying the system, hot water may escape and cause
injuries, particularly scalding!
Drain
The tank are equipped with one 1" / 1 ¼" pipe in the middle on the top that makes
bleeding easy.
Venting
The installation and initial commissioning may be performed only by a recognised in-
stallation company in accordance with the appropriate legal regulations.
Additionally, the whole installation has to be checked for its function and tightness.
It is essential to ll and completely bleed buffer before the rst start-up!
Flush pipes and buffer thoroughly, ll buffer with water, and bleed. Test safety valve by
introducing air.
The tank temperature limitation of the connected boilers may not exceed the maximum
tank temperature (95°C).
Commissioning
If corrosion protection inhibitors are used in the operating water (e.g. with operating
water with a light oxygen content in under-oor heating systems), the protective effect
must be checked.
Servicing
Fit sensors of controls proir to assembly of insulation. Pipework however to be connected
after tting of insulation.
For tanks with sensor channel insert sensor vertically is reached.
An immersion sleeve is already installed in the SPU-1-200 tank.
The thermal insulation of the SPU-1-200 consists of PU hard foam insulation and a
removable foil jacket.
Keep re, soldering ame and/or torches away from the insulation.
Thermal insulation
Druckverlustkurve
Durchuss Heizwasser in l/h
Durchusswiderstand in mbar
SPU-2