EGCP-2 Engine Generator Control Package Manual 26174
66 Woodward
The example below is a typical sequencing screen for a 5-unit system.
Figure 4-11. Sequencing Menu (Multi-Unit)
As displayed on the sequencing screen:
Units 1 3, and 5 are on load with their generator breakers closed.
Next On is unit number 2, which has a network priority of 4.
Next Off is unit number 5, which has a network priority of 3.
Master Unit in this system is the unit with the lowest priority, which is unit
number one.
Units that have active shutdowns will remove themselves from the
sequencing menu until the shutdown condition(s) are cleared.