21COOLIUS A50 / Y50
6.2 Output test
It is possible to activate the devices connected to the mainboard “A” (PWR).
NOTE: Both quick couplers must be installed!
Turn COOLIUS SELECT to select the output to be activated.
Press ENTER to activate the selected OUTPUT.
NOTE: In order to avoid the exit of refrigerant from the vacuum pump outlet or from the oil/UV bottles, the
activation of VP, UV, NO, HO and of all the combinations containing at least one of them, are possible only
when the pressure is lower than 1100 mb.
CP Compressor and Compressor fan
VP Vacuum pump
The HP and LP gauges must show 0 (Zero) bar!
EO Used oil drain valve (EO)
Nitrogen discharge valve (EO2)
Refrigerant analysis circuit oil drain (E3)
NO New oil valve
The HP and LP gauges must show 0 (Zero) bar!
UV Dye tracer valve
The HP and LP gauges must show 0 (Zero) bar!
HO Hybrid oil valve
The HP and LP gauges must show 0 (Zero) bar!
RF Refrigerant valve
XP Recovery valve
LP Separation valve
A1 Aggregate valve
A2 Aggregate valve 2
A3 Nitrogen valve