Troubleshooting
Table 9 provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact
your dealer or Customer Service.
Table 9
Fault Messages
Fault
Number Message Fault Type Cause Solution
F0 Unit is too hot and has shut
down. See guide.
Automatic FET1 Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F2 Unit is too hot and has shut
down. See guide.
Automatic FET2 Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F3 Unit is too hot and has shut
down. See guide.
Automatic Transformer Over
Temperature Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F4 Battery over-temp. Inv/Chg
has shut down. See guide.
Automatic Battery Over Temperature
Shutdown
Clear the fault and attempt restart. Stop
charging, check battery voltage and
temperature. Check for excessive ambient
temperature and adequate ventilation in
the battery compartment.
F5 is too hot and has shut
down. See guide.
Automatic Ambient Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around Freedom SW
3000. Reduce AC loads.

Table of Contents

Other manuals for Xantrex FREEDOM SW 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex FREEDOM SW 3000 and is the answer not in the manual?

Xantrex FREEDOM SW 3000 Specifications

General IconGeneral
BrandXantrex
ModelFREEDOM SW 3000
CategoryInverter
LanguageEnglish

Related product manuals