PROBLEM: AC product will not operate, red inverter
light is
ON; blue Powerpack light is ON.
Possible cause Remedy
AC product(s) connected
are rated at more than the
inverters continuous
power rating; overload
shutdown has occurred.
Use a product with a power
rating less than the inverters
continuous power rating.
AC product is rated less
than the inverters
continuous power rating;
high starting surge has
caused overload shutdown.
Product exceeds inverters
surge capability. Use a
product with starting surge
power within the inverters
capability.
The inverter has
overheated due to poor
ventilation and has shut
down.
Unplug DC cable and allow
inverter to cool 15 minutes.
Remove objects covering
unit. Move the inverter to a
cooler place. Reduce load if
continuous operation is
required. Restart.