VESDA-EVEP-A00-P Product Guide
92 www.xtralis.com
Commissioning checklist for the Remote Display/Relay If used.
Commissioning Checks Done (Y/N) Notes
Zone number configured.
Have checked that no faults are reported.
The alarm and fault relay outputs are wired to the fire
panel.
Test the Remote Display/Relay’s Relay output
connections to the fire panel using the Xtralis VSC Relay
Test command. (Turn each relay on/off individually.) See
below.
Relay 1 Tested (Default assignment = Disable)
Relay 2 Tested (Default assignment = Minor Fault)
Relay 3 Tested (Default assignment = Urgent Fault)
Relay 4 Tested (Default assignment = Alert)
Relay 5 Tested (Default assignment = Action)
Relay 6 Tested (Default assignment = Fire 1)
Relay 7 Tested (Default assignment = Fire 2)
Fire 1 relay connection from Remote Display/Relay to fire
panel tested (using the Xtralis VSC Alarm Test Command
for the detector).
Urgent Fault relay connection from Remote
Display/Relay to fire panel tested (using the Xtralis VSC
Alarm Test Command for the detector).
Client Representative Name
Test witnessed by:
Date:
Hand Over Documents
Copy of this form
ASPIRE Installation Data Pack
ASPIRE Bill of Materials
Configuration printout from Xtralis VSC for each
detector
Configuration printout from Xtralis VSC for each display
module
Smoke test results
Forms required for compliance with local codes and
standards
Customer's Signature
Date:
Commissioner's Signature
Date: