4.6 Preliminary System Check
A preliminary system check is required after installing the VEP-A00 detector, before it is commissioned for
use.
To perform the preliminary system check:
l Power up the detector by connecting the power supply to the Power In terminal.
l Check that the display is functioning.
l Check that the aspirator is functioning by determining whether air is being expelled from the exhaust port.