EasyManua.ls Logo

Xtrails VESDA-E VEP-A00 - Page 49

Xtrails VESDA-E VEP-A00
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA-EVEP-A00-P Product Guide
www.xtralis.com 41
4.3.12 Specify Backup Battery
In the event of a mains power supply disruption, the VEP-A00 detector runs on a backup battery located in the
external power supply (the power supply must be compliant with local fire protection codes and standards).
The size of the battery is determined by:
l local codes and standards
l the total power required by the system
l back up time required
l allowance for reduction in capacity with age
l expected temperature variations
Note: It is recommended that batteries be inspected and changed as per manufacturer’s specifications or
as per local codes and standards.
To facilitate the calculation of the backup battery size, a Battery Calculation Sheet is included below.
Equipment Normal loads@ 24 V DC Full alarm load @ 24 V DC
Load (A) Qty Total Load (A) Qty Total
Detector set to Fan Speed 1 0.29 0.33
Detector set to Fan Speed 5 0.37 0.40
Other 24V Loads Total
(A)
Total
(A)
X X
Normal Hours Alarm Hours
=
Normal Capacity Alarm Capacity
Total Capacity =
Normal + Alarm
Multiply by battery
factor X1.25
Table4-3: Calculating the size of backup battery

Related product manuals