VESDA-EVEP-A00-P Product Guide
iv www.xtralis.com
Regional Regulatory Requirements and Notices
European Installations
EN 54-20
The product must use a power source conforming to EN 54-4 and EN60950-1 Section 2.5.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
l For a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less
than 60 seconds
l For a Class B detector, hole sensitivity must be better than 3% obscuration/m and transport time less
than 90 seconds
l For a Class C detector, hole sensitivity must be better than 8% obscuration/m and transport time less
than 110 seconds
These limits should be verified using ASPIRE during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are
met:
l The minor low and minor high flow thresholds should be set at 85% and 115% respectively
l The flow through the detector predicted by ASPIRE must be greater than 20 L/m.
Additional information:
The VESDA-E VEP-A00 passed the EN 54-20 fire tests with the following configurations:
l Class A with 40 holes and a Fire-1 setting of 0.028% obs/m
l Class B with 80 holes and a Fire-1 setting of 0.027% obs/m
l Class C with 100 holes and a Fire-1 setting of 0.072% obs/m
Only applies to VEP-A00-P.
Japanese Installations
To comply with Japanese local code requirements the WiFi capability shall be disabled.
Product Listings
l UL
l ULC
l FM
l ActivFire
l CE
l VdS
l EN 54-20
l ISO 7240-20
l NF
Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for
the latest product approvals matrix.
Document: 22060_15
Part Number: AD30274-000