Do you have a question about the Xtralis ICAM IFT-15 and is the answer not in the manual?
Device Type | Aspirating Smoke Detector |
---|---|
Detection Method | Laser-based light scattering |
Operating Temperature | -10°C to +55°C |
Voltage Range | 18-30 VDC |
Power Supply | 24 VDC nominal |
Color | White |
Operating Humidity | 10-95% RH, non-condensing |
Compatibility | VESDAnet |
Certification | EN54-20, UL268 |
Tasks to be performed before visiting the customer site to gather necessary information.
On-site tasks including cable checks, power up, and preliminary system checks.
Configuring the system and setting operational thresholds for detectors.
Performing system tests, including pipe integrity and performance tests.
Finalizing documentation and handing over the commissioned system to the client.
Essential documents and tools required before starting the on-site commissioning process.
Details to be entered into the commissioning forms before site visit.
Actions to be taken upon arrival at the customer site to begin commissioning.
Configuring IFT detectors using Xtralis VSC software or a display panel.
Configuring ILS detectors via the user interface panel or Xtralis VSC software.
Configuring IAS detectors through their user interface panel or Xtralis VSC software.
Proving pipe integrity and measuring response time using various smoke test methods.
Testing pipe integrity by introducing smoke and timing detector response.
Using smoke pellets for testing high and enhanced sensitivity environments.
Controlled fire test using polyurethane foam mat for open areas.
Simulating early fire stages by electrically overloading PVC-coated wire.
Testing IFT detector outputs using a diagnostic test via the TEST OUTPUTS menu.
Recording and forwarding test results on commissioning forms.