EasyManua.ls Logo

Xtralis VESDA VFT-15 - Page 43

Xtralis VESDA VFT-15
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA by Xtralis
VESDA VFT Product Guide
www.xtralis.com 37
To install and configure the output module, set applicable parameters according to the following table.
Table 5-11: 8-Channel Output Module Configuration Parameters
Menu Item Parameter Value
SETUP (MODULE n) Set to ANOUT 8
CONFIGURE (MOD n) According to Table 5-12.
(GAIN X) Applies to Smoke only.
G = A/O where:
l G = Gain
l A = Maximum Output Current
l O = Obscuration reading
corresponding to maximum
output current
Examples:
l Set GAIN X to 1 for 20%/m
(1 = 20mA / 20%/m)
l Set GAIN X to 10 for 2%/m
(10 = 20mA / 2%/m)
l Set GAIN X to 100 for 0.2%/m
(100 = 20mA / 0.2%/m)
To access the Setup menu, follow these steps:
1. Press MENU.
2. Use Parameter UP and DOWN buttons to reach SETUP.
3. Press ENTER.
4. Use Value UP and DOWN buttons to enter the Level 2 Access Code.
To access the Configure menu, follow these steps:
1. Press MENU.
2. Use Parameter UP and DOWN buttons to reach CONFIGURE.
Table 5-12: 8-Channel Output Module setup table. Modules are numbered 1 to 5, left to right.
Analog Output Module
1 2 3 4
Channel Channel Channel Channel
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Config Sector Sector Sector Sector
FLOW X 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D
SMOKE X 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D
Note: D = Detector Readings (FLOW X: detector flow; SMOKE X: real time smoke density).

Related product manuals