Computing the Fire 2 Release Point
Computing the Release point is a simple
calculation
Desired release point (2.5%) divided by the #
of holes (8) = Fire 2 (0.3125%ft.)
Hole Sensitivity vs Detector Sensitivity
Adjust FIRE Threshold to achieve HOLE sensitivity