VESDAnet Connection
VESDAnet technical features
Max 100 detectors
Max 200 devices (only 100 detectors max)
RS485 Interface runs over shielded twisted
pair wire up to 1.3km (4,160 ft) in length (from
node to node)
Daisy chain loop configuration, half duplex
VESDAnet is RS-485(15-pin) or USB
Fault tolerant
Cabling can run from any port to any port
(recommend A-B-A-B on larger networks)
Open Loop optional, but not recommended