EasyManuals Logo

Xtralis VESDA VLS User Manual

Xtralis VESDA VLS
367 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
Pipe cutter
Use pipe cutting shears or wheel type plastic tube cutter
Do not use a saw
Remove all dust and shavings created when cutting the pipe
Vacuum piping before connecting to VESDA detector
Bends and clips
Wide radius bends are recommended, as their airflow restriction is
almost negligible
For some regions, only the 90° bends are available based on pipes &
fittings approval
In most cases, 45° bends are acceptable