Codes and Standards Information for Air Sampling Smoke Detection
We strongly recommend that this document is read in conjunction with the appropriate local codes and standards for
smoke detection and electrical connections. This document contains generic product information and some sections may
not comply with all local codes and standards. In these cases, the local codes and standards must take precedence. The
information below was correct at time of printing but may now be out of date, check with your local codes, standards and
listings for the current restrictions.
Regional Regulatory Requirements and Notices
UL
The XAS-1-US is UL Listed as a Smoke Detector for Special Application installations. It is also suitable for Open
Area Protection using the following detector sensitivity ranges:
Detector Application Sensitivity Setting Air Velocity Range(s)
Apollo Series 65 55000-327 Open Area 1.00 %/ft – 1.4 %/ft 0 – 2000 FPM
Apollo XP95 Analog 55000-650 Open Area 1.30 %/ft – 3.43 %/ft 0 – 4000 FPM
Hochiki Analog ALK-V Open Area 1.00 %/ft - 2.06 %/ft l 0 - 2000 FPM – 1.00 %/ft – 2.06 %/ft
l 2000 – 3000 FPM –
1.0 %/ft – 1.5 %/ft
l 3000 – 4000 FPM – 1.0 %/ft
Hochiki SLV-24V Open Area 1.63 %/ft 0 – 300 FPM
Hochiki SLV-24V Duct 1.63 %/ft 0 – 4000 FPM
Hochiki Analog ALN-V(H) Open Area 2.41 %/ft 0 – 300 FPM
Hochiki Analog ALN-V(H) Duct 3.09 %/ft 0 – 4000 FPM
Notifier FSP-851 Open Area 0.5 – 3.80 %/ft 0 – 300 FPM
Notifier FSP-851 Duct 0.5 – 1.95 %/ft 0 – 4000 FPM
System Sensor 2251B or
l Notifier - Fire Warden NP-100
l Gamewell/FCI ASD-PL2F
l Silent Knight IDP-PHOTO
l Silent Knight SK-PHOTO
l Firelite SD355
l Honeywell TC806B1076
l JCI 2951J
Open Area 0.5 – 3.50 %/ft 0 – 300 FPM
System Sensor 2251B or
l Notifier - Fire Warden NP-100
l Gamewell/FCI ASD-PL2F
l Silent Knight IDP-PHOTO
l Silent Knight SK-PHOTO
l Firelite SD355
l Honeywell TC806B1076
l JCI 2951J
Duct 0.5 – 3.08 %/ft 0 – 4000 FPM
Siemens Analog HFP-11 Open Area 1.00 %/ft – 1.34 %/ft 0 – 2000 FPM
Siemens Detectors
l FDO421
l OP921
Open Area "Sensitive”
1.4 %/ft.
0 – 4000 FPM
Siemens Detectors
l FDO421
l OP921
Duct "Duct"
2.3 %/ft.
0 – 4000 FPM
Siemens Detectors
l FDOOT441
l OOH941
l FDOOTC441
l OOHC941
Open Area "Computer Room”
2.0 %/ft.
0 – 4000 FPM
Xtralis Pty Ltd Xtralis XAS-1-USProduct Guide
www.xtralis.com iii