Xtralis XAS-1-USProduct Guide Xtralis Pty Ltd
Detector Application Sensitivity Setting Air Velocity Range(s)
Siemens Detectors
l FDOOT441
l OOH941
l FDOOTC441
l OOHC941
Duct "Duct"
2.0 %/ft.
0 – 4000 FPM
ULC
The XAS-1-US unit is ULC Listed as a Smoke detector for special application installations. It is also suitable for
Open Area and Duct applications using the following settings:
Detector Application Sensitivity Setting Air Velocity Range(s)
Hochiki SLV-24V Open Area 1.93 %ft 0 – 300 FPM
Hochiki Analog ALN-V(H) Open Area 1.87 %ft 0 – 300 FPM
Siemens Analog HFP-11 Open Area “Computer Room”
2.25 %/ft
0 – 300 FPM
Siemens Analog HFP-11 Duct “Warehouse”
3.4 %/ft
0 – 4000 FPM
Notifier FSP-851A Open Area 0.5 – 3.70 %/ft 0-300 FPM
Notifier FSA-851A
Johnson Controls A2951JA
Open Area 0.5 %/ft - 3.77 %/ft 0-300 FPM
Notifier FSA-851A
Johnson Controls A2951JA
Duct 0.5 %/ft - 3.77 %/ft 0 – 4000 FPM
System Sensor 2251BA or
l Notifier - Fire Warden NP-100A
l Gamewell/FCI ASD-PL2FA
l Firelite SD355A
l Honeywell TC806B1076CDN
l JCI 2951JA
Open Area 0.5 %/ft - 2.87 %/ft 0-300 FPM
Siemens Detectors
l FDO421
l OP921
Open Area “Sensitive”
1.4 %/ft.
0 – 4000 FPM
Siemens Detectors
l FDO421
l OP921
Duct “Duct”
2.3 %/ft.
0 – 4000 FPM
Siemens Detectors
l FDOOT441
l OOH941
l FDOOTC441
l OOHC941
Open Area “Computer Room”
2.0 %/ft
0 – 4000 FPM
Siemens Detectors
l FDOOT441
l OOH941
l FDOOTC441
l OOHC941
Duct “Duct”
2.0 %/ft.
0 – 4000 FPM
iv www.xtralis.com