EasyManua.ls Logo

Yale HSA3095

Yale HSA3095
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
¥
Do not position a PIR to look directly at a door
protected by a door contact, this could cause the
door contact and PIR radio signals to be
transmitted at the same instant when entering,
cancelling each other out.
¥ Ensure the jumper is in the normal off position
when testing is finished, otherwise low battery
and tamper conditions will not be shown.
Door/Window contact
1 Ensure the jumper
switch is in the test
on position.
¥ In this position the
indicator light will
illuminate every time
the door contact is
operated.
2 Fit as described in
Mounting methods,
mounting the
detector base on the
frame and aligning
the magnet by the
arrow as shown.
¥ The magnet should not be more than 8mm from
the detector when the door is closed.
¥
Ensur
e the tamper switch spring is positioned so
that it makes contact with the mounting surface
through the tamper switch aperture.
¥ If the door contact cannot be mounted on the
door frame, use the HSA3090 multiple
door/window contact accessory kit with a length
of wire to mount the door contact remotely (see
page 17).
¥ When fitting to a window, fix the magnet to the
moving part and the detector to the frame.
3 Fix the detector on its base and secure with
s
crew. Test it by opening and closing the door or
window. The light will flash when an open
condition is detected.
4 Remove the detector, put the jumper switch in
the normal off position. Screw the detector back
onto its base.
¥ When the jumper is in the normal off position
the indicator light will normally be off. It will only
light if there is a problem, either a low battery or a
tamper condition.
¥ Ensure the jumper is in the normal off position
when testing is finished, otherwise low battery
and tamper conditions will not be shown.
Smoke detector
1 Unscrew the fixing plate from the smoke detector
by turning the plate anti-
clockwise.
2 Using the two holes of the
ceiling mounting bracket as a
template, mark the position of
the holes.
3 Drill 2 holes and fix into place
with the 2 screws and plugs
provided.
4 Hook the smoke detector onto
the bracket and secure by
tur
ning in a clockwise dir
ection.
Flood detector
1 Use the two fixing holes on the product as a
template, mark the position of the holes.
2 Drill 2 holes and fix into place with the 2 screws
and plugs provided.
Installation is complete.
Door/
Window
Frame
Align
8mm (max)
Surface fixing
holes x 2

Related product manuals