3 Product and functional description
09.2019 15
ba-o.4.1.3-en-2.2-y
3.6.2 Sensor errors
The load signal (+IN/-IN) from the DMS sensor is processed internally in the SLE 3 on
two channels and monitored permanently.
The following three types of sensor errors are detected
broken cable
short circuit
differential error between the internal measuring amplifiers in the device internal
error.
NOTICE
See chapter "Error messages" on error diagnosis and correction.
In all three cases of sensor errors the output relays K↑ and K↑↑ are switched off in
dependence on the actuation of the safety inputs S↑ and S↕↕ and indicated as error
code by the device LEDs.
The maximum response time for cut-off of the outputs is:
when input S↑ active = 850 ms
when input S↑ not active = 1950 ms
A sensor error is acknowledged when:
the cause of the error no longer exists
and
the sensor signal is within the function limits and
lift S↑ is not actuated.
WARNING
It remains possible to carry out the downwards movement (switching of the out-
puts K↓ and K↓↓) in the case of an overload or sensor error so that a suspended
load can be put down if necessary!
3.7 Control and monitoring functions
3.7.1 Actuation
The safety inputs S↑, S↓ and the input S↕↕ are read in in relation to N.
S↑ and S↓ are kept in the device on two channels in both controllers and evaluated
according to Category 2 Performance Level d.
Actuation of S↕↕ is only recognised if the corresponding direction S↑ or S↓ is active at
the same time.
If S↑ or S↓ is actuated from idle state, the SLE 3 switches the respective safety output
K↑ or K↓ after a maximum delay time of 300 ms.