5 Installation Procedure
YASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual 19
Communication Cable Specifications
Only use cables recommended for Modbus TCP/IP. Using a cable not specifically recommended may cause the
option or drive to malfunction.
The use of CAT5e or equivalent Shielded Twisted Pair (STP) cable is recommended.
Connection Diagram
Figure 19 Wiring Diagram
15. Attach the option cover by aligning the tabs with the mounting holes, seat the front cover into place, and tighten
the screw on the front.
Figure 19
Figure 20 Attach the Option Cover
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables
are pinched between the front covers and the drive when replacing the covers.
16. Set drive parameters in Table 6 for proper option performance.
<1> The ground wire provided in the option shipping package must be connected during installation.
V1000
M
U
V
W
R
S
T
SI-EN3/V
EtherNet/IP
Option
FE
<1>
EtherNet/IP Master
EtherNet/IP Cable
MotorPower
V1000
Tabs should line up
V1000