5 Installation Procedure
18 YASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual
12. Attach the option to the drive. Properly seat the tabs on the left and right sides of the option to the drive case.
Figure 16
Figure 16 Connect the Option
13. Connect the ground wire at the option ground terminal. Tighten the screw to 0.5 to 0.6 Nxm or (4.4 to 5.3 in lbs)
using an M3 Phillips screwdriver.
Figure 17
Figure 17 Connect the Ground Wire to the Option
14. To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair Cat 5e cable(s) into the
modular connector port.
Note: Do not connect or disconnect the communication cable while the drive is powered up or while the drive is in operation. Failure to
comply may cause a static discharge, which will cause the option card to stop working properly. Cycle power on the drive and
option card to reestablish functionality.
Figure 18
Figure 18 Communication Cable Port
Line up tabs
Line up tabs
V1000
Option ground
terminal
V1000
V1000