10 Electrical Installation
YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps EN 19
Figure 10.1 Standard Drive Connection Diagram
*1 Set the wiring sequence to de-energize the drive with the fault relay output. Set L5-02 = 1 [Fault Contact at
Restart Select = Always Active] to de-energize the drive when the drive outputs a fault during fault restart
when using the fault restart function. Be careful when using a cut-off sequence. The default setting for L5-02
is 0 [Active Only when Not Restarting].
*2 Connect peripheral options to terminals -, +1, +2, B1, and B2.