9 Electrical Installation
YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide 27
A - Strain relief
Figure 9.4 Strain Relief Example
Table 9.2 Recommended Wiring Tools
Screw Size Screw Shape Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model Manufacturer
M4 Slotted (-) Bit SF-BIT-SL 1,0X4,0-70 PHOENIX CONTACT
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 lbf∙in))
-
M5
*1
Slotted (-) Bit SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
Wire Gauge ≤
25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 lbf∙in))
Wire Gauge ≤
25 mm
2
(AWG 10): -
Wire Gauge ≥
30 mm
2
(AWG 8): -
Wire Gauge ≥
30 mm
2
(AWG 8):
4.1 - 4.5 N∙m
(36.3 - 39.8 lbf∙in)
*2
*3
M6
Hex socket cap
(WAF: 5 mm)
Bit SF-BIT-HEX 5-50 PHOENIX CONTACT -
5 - 9 N∙m
(44.3 - 79.9 lbf∙in)
*2
*3
Minus (-) Bit SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT -
3 - 3.5 N∙m
(26.6 - 31.0 lbf∙in)
*2
*3
M8
Hex socket cap
(WAF: 6 mm)
Bit SF-BIT-HEX 6-50 PHOENIX CONTACT -
8 - 12 N∙m
(70.8 - 106.2 lbf∙in)
*2
*3
M10
Hex socket cap
(WAF: 8 mm)
Bit SF-BIT-HEX 8-50 PHOENIX CONTACT -
12 - 14 N∙m
(106.2 - 123.9 lbf∙in)
*2
*3
*1 When wiring drive models 2047, 4075, and smaller, select the correct tools for the wire gauge.
*2 Use 6.35 mm (0.25 in) bit socket holder.
*3 Use a torque wrench that can apply this torque measurement range.
Main Circuit Terminal Block Wiring Procedure
Remove the keypad and front cover before wiring the main circuit terminal block.
1. Pull the wiring cover away from the drive to remove it.
A - Wiring cover
Figure 9.5 Remove the Wiring Cover
EN