EasyManua.ls Logo

YASKAWA GPD 506/P5 - Page 26

YASKAWA GPD 506/P5
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The Message Format 6-5
Fault Response Message
The fault response message contains the same slave address as the command message,
indicating to the master which slave is responding.
The function code of a fault response message is actually a value of 80h plus the original function
code of 03h. This indicates to the master that the message is a fault response message, instead of
a normal response message.
The error code indicates where the error occurred in the command message. The value of 2h in the
error code field of this fault response message, indicates that the command message requested
data be read from an invalid register. A complete listing of the error codes is shown in Chapter 8,
Troubleshooting and Error Codes.
A CRC-16 value is generated from a calculation using the values of the address, function code, and
error code sections of the message. The procedure for calculating a CRC-16 value is described at
the end of this chapter. When the master receives the fault response message it calculates a CRC-
16 value and compares it to the one in the CRC-16 field of the fault response message. If these two
CRC-16 values are the same the master has received the proper fault response message.
02h
SLAVE ADDRESS
80h + FUNC. CODE
83h
02h
30h
F1h
CRC-16
LOWER
UPPER
ERROR CODE

Related product manuals