EasyManua.ls Logo

YASKAWA GPD 506/P5 - Table 9-3. Set up for Digital Operator Control

YASKAWA GPD 506/P5
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Command Priority 9-5
Table 9-3: Set up for Digital Operator Control
Table three indicates the functions or commands that can be accessed via serial communication,
external terminals, or the digital operator when drive parameter n002 is set up for digital operator
control (n002 = 0, 2, or 4). The ‘O’ indicates that the function is Operable from that source, and
n/a’ indicates that the function is not available from that source.
From Data
Code
Bit
No.
Data Description Function
Availability
001h
0
Run Command
n/a
1
Forward / Reverse
n/a
2
External Fault
O
3
Fault Reset
O (1)
4
Multi-function Input (terminal S3)
O
5
Multi-function Input (terminal S4)
O
SERIAL
6
Multi-function Input (terminal S5)
O
COMM.
7
Multi-function Input (terminal S6)
O
8-15
unused
-
003h-
unused
-
008h
009h
0
Multi-function Output 1 (MA - MC)
O (3)
1
Multi-function Output 2 (M1 - M2)
O (4)
2
unused
-
3-7
unused
-
Forward Run (2 wire); Run Command (3 wire)
n/a
Reverse Run (2 wire); Stop Command (3 wire)
n/a
EXTERNAL
Multi-function input terminal S2
(2)
TERMINALS
Multi-function input terminal S3
(2)
Multi-function input terminal S4
(2)
Multi-function input terminal S5
(2)
Multi-function input terminal S6
(2)
Run Command
O
DIGITAL
Stop Command
O
OPERATOR
Fault Reset
O (1)
Local / Remote
n/a
1. Notes:
2. Effective only when in stopped condition.
3. The availability of the multi-function input terminals vary depending upon the settings of n036, n037, n038, n039,
and n040 (the multi-function input settings). See technical manual TM 4506.
4. Effective when n041 is ‘15’.
5. Effective when n042 is ‘15’.

Related product manuals