Command Priority 9-3
Table 9-1: Set up for Serial Communication Control
The first table indicates the functions or commands that can be accessed via serial communication,
external terminals, or the digital operator when drive parameter n002 is set up for serial
communication (n002 = 6, 7, or 8). The ‘O’ indicates that the function is Operable from that source,
n/a’ indicates that the function is not available from that source.
From Data
Code
Bit
No.
Data Description Function
Availability
001h
0
Run Command
O
1
Forward / Reverse
O
2
External Fault
O
3
Fault Reset
O (1)
4
Multi-function Input (terminal S3)
O
5
Multi-function Input (terminal S4)
O
SERIAL
6
Multi-function Input (terminal S5)
O
COMM.
7
Multi-function Input (terminal S6)
O
8-15
unused
-
003h-
unused
-
008h
009h
0
Multi-function Output 1 (MA - MC)
O (2)
1
Multi-function Output 2 (M1 - M2)
O (3)
2
unused
3-7
unused
-
Forward Run (2 wire); Run Command (3 wire)
n/a
Reverse Run (2 wire); Stop Command (3 wire)
n/a
EXTERNAL
Multi-function input terminal S2
(4)
TERMINALS
Multi-function input terminal S3
(4)
Multi-function input terminal S4
(4)
Multi-function input terminal S5
(4)
Multi-function input terminal S6
(4)
Run Command
n/a
DIGITAL
Stop Command
O (5)
OPERATOR
Fault Reset
O (1)
Local / Remote
O (1,6)
Notes:
1. Effective when run command received from PLC is ‘0’ while in stopped condition.
4. The availability of the multi-function input terminals vary depending upon the settings of n036, n037, n038, n039, and
n040 (the multi-function input settings). See technical manual TM 4506.
5. Effective only when n008 is ‘1’.
6. Effective only when n007 is ‘1’.